Control TechniquesFault codes

Unidrive SP fault codes

Every trip the Control Techniques Unidrive SP can display, listed by the trip number shown in parameter 10.20, with what each one means. Taken from the Unidrive SP Advanced User Guide.

Unidrive SP trip table

Listed by the trip number shown in parameter 10.20, so you can cross-reference the drive over serial or from the keypad. Grouped rows cover the user-defined trip ranges and the hardware trips, which carry no trip number.

Unidrive SP fault indications and what they mean
Trip no.DisplayMeaning
Main drive trips
1UVDC bus undervoltage. Self-resetting when the bus rises above the restart level — 330 V trip and 425 V reset on a 400 V drive
2OVDC bus overvoltage — peak level exceeded, or above the maximum continuous level for 15 seconds. Deceleration too fast, braking resistor open, or a regenerative load
3OI.ACInstantaneous output overcurrent: peak output current above 222% of rating — output short, motor insulation, or IGBT failure
4OI.brBraking IGBT instantaneous overcurrent — fault in the braking resistor circuit
5PSInternal power supply fault on the drive
6EtExternal trip from a digital input on terminal 31
7O.SPdMotor speed has exceeded the overspeed threshold
8PS.10V10V user power supply overload on the control terminals
9PS.24V24V user power supply overload on the control terminals
10br.thBraking resistor over temperature from the hardware thermal monitoring
11 – 18tunE1 – tunEAutotune and mechanical load measurement failures — the sub-trip identifies the stage that failed
19It.brBraking resistor I²t overload — accumulator value in Pr 10.39
20It.ACOutput current I²t overload — accumulator value in Pr 4.19
21O.ht1Power device over temperature from the software thermal model
22O.ht2Heatsink over temperature from the measured heatsink sensor
23O.CtLControl board over temperature
24thMotor thermistor trip
25thSMotor thermistor short circuit
26O.Ld1Digital output overload — total current from the 24V supply and digital outputs above 200 mA
27O.ht3Drive over temperature from the thermal model — the drive stops the motor before tripping
28cL2Analogue input 2 current loss in current mode
29cL3Analogue input 3 current loss in current mode
30SCLRS485 serial comms loss to the remote keypad
31EEFEEPROM checksum failure — defaults loaded, cannot be reset until a load-defaults code is entered
32PHAC input phase loss or large supply imbalance, detected from DC bus ripple
33rSFailure to measure motor resistance during autotune, or when starting in open loop vector mode 0 or 3
34PAdKeypad removed while the drive is taking its speed reference from the keypad
35CL.bitTrip initiated from the control word, Pr 6.42
36SAVE.ErUser save parameters in the EEPROM are corrupt
37PSAVE.ErPower-down save parameters in the EEPROM are corrupt
38t038User defined trip — raised by the onboard PLC or an option module
39L.SYnCDrive failed to synchronise to the supply voltage in Regen mode
40 – 89t040 – t089User defined trips, raised from the onboard PLC or an option module program
Onboard PLC trips
90 – 98UP div0 – UP ACCOnboard PLC program errors: divide by zero, non-existent parameter, write to a read-only parameter, read of a write-only parameter, out-of-range write, overflow, requested trip, undefined trip, or program file inaccessible
99, 101t099, t101User defined trips
Power module trips
102 – 110Oht4.P – Unid.PPower module trips: rectifier over temperature, braking IGBT overcurrent, output overcurrent, heatsink over temperature, overvoltage, phase loss, power supply failure, IGBT on-state overcurrent, and unidentified module trip
111ConF.PThe number of power modules installed no longer matches the value stored in Pr 11.35
112 – 160t112 – t160User defined trips
Feedback and SMARTCARD trips
161 – 167Enc11 – Enc17Encoder auto-configuration and comms trips for SINCOS, Hiperface and EnDat feedback devices
168 – 174t168 – t174User defined trips
175 – 187C.Prod – C.TyPSMARTCARD trips: data blocks not compatible with this product, electronic nameplate error, boot error, card busy, data location occupied, option modules differ, read-only card, corrupted data, empty location, card full, read/write fail, rating mismatch, parameter set not compatible
188C.cPrSMARTCARD data is not compatible with this drive
189 – 196EnC1 – EnC8Drive encoder trips: power supply overload, wire break, phase offset incorrect while running, comms failure, checksum or CRC error, encoder reported error, initialisation failed, auto-configuration failed
199dEStTwo or more parameters are writing to the same destination parameter
200 – 204SL1.HF – SL1.dFSolutions Module in slot 1: hardware fault, watchdog failure, module detected fault, module removed, module changed
205 – 209SL2.*Solutions Module in slot 2 — same set of trips as slot 1
210 – 214SL3.*Solutions Module in slot 3 — same set of trips as slot 1
215, 216SL.rtd, t216Solutions Module rating trip, and a user defined trip
217 – 232HF17 – HF32Hardware trips: multi-module thermistor and interconnect faults, temperature feedback multiplexing, power stage recognition and serial code errors, current feedback offset, power stage and control board thermistors, DCCT wire break
Hardware trips
—HF01 – HF16Control board hardware faults — CPU, memory, bus, watchdog and stack failures. No trip number and cannot be reset; the drive needs replacing or the control board repairing

Trip strings vary slightly with software version. If your display shows something not listed here, send us a photo of the keypad and we will identify it.