Control TechniquesFault codes

Unidrive M fault codes

Every trip the Control Techniques Unidrive M compact drives can display, listed by the trip number shown in parameter 10.020. Taken from the Unidrive M200/M201 Control User Guide, which covers the trip set used across the M100 to M300 range.

Unidrive M trip table

Listed alphabetically by the string shown on the display, with the trip number it reports in parameter 10.020. Trips marked with a dash carry no trip number. M400 and above add their own encoder, option module and regen trips on top of this set.

Unidrive M fault indications and what they mean
Trip no.DisplayMeaning
Status
—UVUnder voltage — a drive status rather than a trip on the compact M drives: the bus is below the working level, so the drive cannot be enabled. Self-clears when the supply recovers
Drive trips
2OVDC bus voltage above the peak level, or above the maximum continuous level for 15 seconds — deceleration too fast, braking resistor open, or a regenerative load
3OI.ACInstantaneous output overcurrent — output current above the drive maximum. Cannot be reset for 10 seconds. Check output cabling, motor insulation and the IGBT power stage
4OI.brBraking IGBT overcurrent — short circuit protection in the braking IGBT has operated
5PSUInternal power supply fault on the drive
6EtExternal trip from a digital input, or a value of 6 written to Pr 10.038
7O.SPdMotor frequency has exceeded the over-frequency threshold
8U.OIUser overcurrent trip — output current above the level set in Pr 04.041
10th.brBraking resistor over temperature from the hardware thermal monitoring
11tun.1Required speed could not be reached during autotune
13tun.3Measured inertia has exceeded the parameter range
18tun.SAutotune test stopped before completion
19It.brBraking resistor I²t overload — check Pr 10.030, 10.031 and 10.061 against the resistor fitted
20It.AcOutput current I²t overload — motor overload, blocked load or incorrect motor rated current
21Oht.IInverter over temperature from the thermal model — trips at 145 °C, resets at 139 °C
22Oht.PPower stage over temperature — heatsink fan, airflow or a blocked filter
24thMotor thermistor over temperature on terminal 14 — check the threshold in Pr 07.048 and the thermistor continuity
25thSMotor thermistor short circuit or low impedance (below 50 Ω)
26O.Ld1Digital output overload — total current from the digital outputs and 24V supply is too high
27Oh.dcDC bus over temperature — the drive stops the motor before tripping
28cL.A1Analogue input 1 current loss in 4-20 mA or 20-4 mA mode — signal below 3 mA or a wiring fault
30SCLControl word watchdog has timed out
31EEFDefault parameters have been loaded — the parameter bank or EEPROM checksum has failed
32PH.LoSupply phase loss or large supply imbalance, detected from DC bus ripple
33rSMeasured stator resistance has exceeded the parameter range during autotune
34PAdKeypad has been removed while the drive is taking its reference from the keypad
37Pd.SPower down save error — the parameters saved at power-down could not be verified
90LF.ErCommunication lost or excessive errors between the power, control and rectifier modules
92OI.SnSnubber overcurrent detected
93Pb.ErCommunication lost between the control and power processor
97d.ChDrive parameters are being changed while the drive was commanded to enable — defaults load, mode change or card transfer
98Out.POutput phase loss detected
173FAn.FFan failure — not fitted, not connected or obstructed. Cannot be reset for 10 seconds
NV Media Card trips
185C.AccNV Media Card write fail
178C.byNV Media Card cannot be accessed because an option module is using it
188C.cPrFile or data on the card is different to the one in the drive
179C.d.ECard data location already contains data
183C.dAtCard data location does not contain any data
182C.ErrCard data structure error
184C.FuLNV Media Card full
175C.PrCard data blocks are not compatible with the drive derivative
181C.rdoCard has the read-only bit set
174C.SLOption module file transfer to or from the card has failed
187C.tyPCard parameter set is not compatible with the current drive mode
Measurement and protection trips
189OI.A1Analogue input 1 current above 24 mA
199dEStTwo or more parameters are writing to the same destination parameter
219Oht.CControl stage over temperature — cooling fan control is off; the option module goes to standby
220P.dAtPower system configuration data error
225Cur.OCurrent feedback offset too large to trim — measurement circuit fault, usually with current flowing at power-up
226So.StSoft-start relay failed to close, or its monitoring circuit has failed
227r.AllRAM allocation error
228OI.SCOutput phase short circuit detected
231Cur.cCurrent calibration range error in the current measurement circuit
232dr.CFDrive configuration — the hardware ID does not match the user software ID
234StoNo Safe Torque Off board fitted, or the internal STO board is not fitted correctly
235Pb.HFPower board hardware fault
236no.PSNo power board detected
237FI.InFirmware incompatibility — user firmware does not match the power firmware; reflash with Unidrive M Connect
245Pb.btPower board is in bootloader mode
Derivative and option module trips
246dEr.EDerivative file missing, invalid or not matched to the control board hardware
247Fi.ChFile changed
248dEr.IDerivative product image error — CRC, memory allocation, task timing or parameter table fault
250r.b.htHot rectifier or brake — thermal model has flagged the rectifier or braking IGBT
200SL.HFOption module in slot 1 hardware fault — the sub-trip number gives the cause
201SL.tOOption module in slot 1 started the watchdog function and failed to service it
202SL.ErOption module in slot 1 has detected a fault — see the module user guide for the sub-trip
203SL.nFOption module in slot 1 has been removed since the last power up
204SL.dFOption module in slot 1 is a different type to the one installed when parameters were last saved
218tH.FbInternal drive thermistor has failed — open or short circuit inside the drive
Hardware trips
—HF01 – HF23Control board hardware trips: CPU address, bus and usage faults, watchdog failure, interrupt crash, stack overflow, non-volatile memory comms, internal flash failure and firmware CRC errors. No trip number, cleared only by cycling power

Trip strings vary slightly with software version. If your display shows something not listed here, send us a photo of the keypad and we will identify it.

24/7 emergency call-outs

Unidrive M tripping?

Send us the trip code for a free fault assessment, or call 0161 399 0042 for 24/7 emergency call-outs. Fixed-price quote within 24 hours of your unit arriving, with a 12-month warranty.